Building Technologies Basic Documentation LMV27... CC1P7541en
28 Error code list (of all LMV2 / LMV3 types) 17.12.2018
Error
code
Diagnostic code Meaning for the LMV27 Recommended measures or causes
Check that the oil is preheated correctly
50 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
51 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
55 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
56 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
57 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
58 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
60 # Internal error: No valid load controller source
0 Internal error: No valid output source
Make a reset; if error occurs repeatedly, replace the LMV27
1 Analog output preset valid – prevention of startup
1. Check wiring of analog predefined output to see if there is an open-circuit / loose contact.
2. When the trim function is activated (parameter 530), the default output must not be on invalid if
the Modbus communication (parameter 148 / 149) is interrupted.
2 Analog output preset valid – default output low-fire
1. Check wiring of analog predefined output to see if there is an open-circuit / loose contact.
2. When the trim function is activated (parameter 530), the default output must not be on invalid if
the Modbus communication (parameter 148 / 149) is interrupted.
Note!
This information is provided in connection with the thermal shock protection function
(manual interruption of 4...20 mA analog input)
61 Fuel
Chg
# Fuel changeover
Fuel
Chg
0 Fuel 0
No error - change to Fuel 0
Fuel
Chg
1 Fuel 1
No error - change to Fuel 1
62 Fuel
Err
# Invalid fuel signals / fuel information
Fuel Err 0 Invalid fuel selection (Fuel 0 + 1 = 0)
Check wiring to see if there is an open-circuit
Note
Curves cannot be set
Fuel Err 1 Different fuel selection between the µCs
Make a reset; if error occurs repeatedly, replace the LMV27
Fuel Err 2 Different fuel signals between the µCs
Make a reset; if error occurs repeatedly, replace the LMV27
Fuel Err 3 Invalid fuel selection (Fuel 0 + 1 = 1)
Check wiring for short-circuit
Note
Curves cannot be set.