209/219
Building Technologies Basic Documentation LMV27... CC1P7541en
28 Error code list (of all LMV2 / LMV3 types) 17.12.2018
Error
code
Diagnostic code Meaning for the LMV27 Recommended measures or causes
Bit 3
Valency 8..15
Standardized speed undefined
Carry out speed standardization.
If no speed signal is present in pneumatic operation, the parameters 667, 668, 669.0 / 669.1 must
be set to
invalid to switch off the start prevention.
Bit 4
Valency 16..31
Backup / restore was not possible
202 # Internal error operating mode selection Redefine the operating mode (parameter 201)
203 # Internal error
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the LMV27
204 Phase number Program stop Program stop is active (no error)
205 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
206
0
Inadmissible combination of LMV27
(LMV27 - AZL2)
207 # Version compatibility LMV27 - AZL2
0 LMV27 version too old
1 AZL2 version too old
208 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
209 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
210
0 Selected operating mode is not released for the LMV27
Select a released operating mode for the LMV27
240 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
242 # Invalid parameterization
0 Invalid setting parameter 277
Set parameter 277 to a valid value
1 Invalid setting parameter 377
Set parameter 377 to a valid value
245 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27
250 # Internal error Make a reset; if error occurs repeatedly, replace the LMV27