Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 29 Parameter list LMV36... 25.09.2013
Par. Parameter Number of Type Edit Value range Resolution Default Password level
no. LMV36... elements Min Max setting
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod. sep. circulation ¹)
24 = Ho 2-stage sep. circulation ¹)
25 = Ho mod. without circulation ¹)
26 = Ho 2-stage without circulation ¹)
27 = Ho 3-stage without circulation ¹)
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0
208 Program stop
0 = inactive
1 = PrePurgP (Ph24)
2 = IgnitPos (Ph36)
3 = interval 1 (Ph44)
4 = interval 2 (Ph52)
1 Selection Edit 0 4 1 0 SO (BA)
210 Alarm in the event of start prevention
0 = inactive
1 = active
1 Selection Edit 0 1 1 1 SO