TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section5 Page4 SCCInc.
Ingeneral,alinereactorisrecommendedifthesupplycapacity(kVA)ofthetransformerfeedingthe
driveisgreaterthanorequalto10timesthecapacity(kVA)ofthedrivefortransformers600kVAand
larger.
Figure51notes:
1. DrivepowerisshowninHPratherthankVA.Thisconversioncanbedoneassumingapowerfactor
ofunity(1)andnegligib
lelossesduetoefficiency.
2. Transformerslessthan600kVAhavehighenoughimpedance(“soft”enough)sothatlinereactors
aretypicallynotnecessary.
Example1:A25HPdriveisbeingfedbyan800kVAtransformer.Isalinereactorrequired?
Assumptions:
Thepowerfactorisunity(powerfactor=1)
Lossesduetoefficiencyandwiringarenegligibl e
1. Converthorsepowertokil
owatts:25HPx0.745HP/kW=18.63kW
2. ConvertkilowattstokVA:kW=kVA*Pf(Pfispowerfactor,whichisassumedtobe1inthis
example
)
Thus,a25HPdriveis18.63kVA.
3. CalculatethekVAratio:800kVA/18
.63kVA=42.94
Sincearatioof42.94isgreaterthan10,andthetransformerislargerthan600kVA,aline
reactorwillbenecessaryforthisapplication.Thesameconclusioncanalsobearrivedatby
usingFigure51.
Example2:A10
HPdriveisfedbya400kVAtransformer.Isalinereactorrequired?
Usingthesameassumptionsandcalculationasexample1,thekVAratiois53.7,butthetransformeris
smallerthan600kVA,soalinereactorisnotnecessary.Th
esameconclusioncanalsobearrivedatby
usingFigure51.
OutputWiring/LoadReactors
WhentheVFD/motorarerunning,highlevelsofelectricalnoiseareproducedonthewiringbetween
theVFDandthemotor.Thisisduetothefactthatmodifiedsinewavesprodu
cedbythedriveIGBTsare
basicallyhighfrequency/highvoltageDCpulses.Theseoutputwiresmustbeenclosedinsometypeof
shielding(metallicconduitormetalshielded cable)tomitigateradiatedelectricalnoise.
WirelengthbetweentheVFDandthemotorshouldbekepttoless than 150
feetifpossibleduetothe
reflectedwave/standingwavephenomenonandvoltageovershootphenomenon.Bothofthese
phenomenaarerathercomplex,andareafunctionofthewirelengthfromtheVFDtothemotor.The
reflectedwave/standingwavephenomenonandvoltageovershootphenom
enoncandamagenon
inverterdutymotorwindingsovertimeduetothehighpeakvoltagesthatthesephenomenacan
produce.