TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section6 Page26SCCInc.
IfonlytheO
2
alarmfunctionistobeuse dand theO
2
trimhasnotbeencommissioned,afewkey
parametersmustbeset.Theseare:
1. O2MaxValue‐settothemaximumsafe%O
2
(wet)forallpoints.
2. O2Alarmcurve‐entertheminimumsafe%O
2
(wet)foreachpoint.
3. TauLowFireOEM‐thedelaytimeoftheburner/boileratlowfire
4. TauHighFireOEM‐thedelaytimeoftheburner/boilerathighfire
5. OptgMode‐settoO2Limiter
IftheO
2
trimhasnotbeencommissioned,itwillbenecessarytomanuallyenterTauLowFireOEMand
TauHighFireOEM.TheseTautimesdonothavetobeasaccurateasiftheO
2
trimwasbeingused.
ThesecanbemanuallytimedbyusingtheO
2
readingontheAZL(recommended),ortypicalvaluescan
beused.HigherturndownburnerswillproducelongerlowfireTautimes.Typically,fora5to1
turndownburner,TauLowFireOEMisbetween1020seconds.TauHighFireOEMistypically4
secondsorless.
HowtheO
2
isMeasuredwiththeQGO20SensorandPLL52Module
TheQGO20isaZirconiumtypesensorthatisheatedtoapproximately1292°F.Thehightemperatures
allowoxygentodiffusethroughtheZirconiumcellandproduceamillivoltsignal.Thismillivoltsignalis
referredtoastheNernstVoltage.TheNernstVoltagethatisproducedforagiven%O
2
isdependenton
theconcentrationofoxygenandthetemperatureof theZirconiumcell.ThePLL52modulereads both
theNernstVoltageandthetemperatur eoftheZirconiumcell.Withthisinformation,the%O
2
canbe
accuratelydeterminedandsentbacktotheLMV52overCANbus.
AswellastakingthemillivoltsignalsandconvertingthesetoCANbusdata,thePLL52alsoservesasthe
controllerfortheZirconiumcell'sheatingelement.ThePLL52isalsoaplacetoconnectthecombustion
airtemperaturesensorandthestackgastemperaturesensor.
ThreemillivoltsignalsoriginateintheQGO20:
1. NernstVoltagefromtheZirconiumoxideO
2
cell terminalsB1andM
2. O
2
cellthermocouplesignalterminalsB2andM
3. Coldjunctionthermocouplecompensation terminals G2andU3
ThesethreemillivoltsignalsbetweentheQGO20andthePLL52mustberuninaseparateconduitand/
orashieldedcable.
SeeSection2forcompletedetailsonwiringtheQGO20tothePLL52.
HighvoltagewiresarealsoconnectedfromthePLL52totheQGO20fortheheater.Itisveryimportant
thatthesewiresareruninaseparateconduitawayfromthemillivoltsignals.
NOTE:NeverconnecttheQGO20heaterdirectlytolinevoltage!Permanentdamagewillresulttothe
heatingelementandthesensor.HighvoltagewiresfortheheatertotheQGO20mustcomefromthe
PLL52module.SeeSection2formoreinformation.
Also,duetopossibleinterferenceonthemillivoltsignals,thePLL52mustbeinstalledwithin30feetof
theQGO20.