OpenSafetyLoopErrorCode21
Thesafetyloopismeantonly for safety limitssuchas an auxiliary lowwatercutoutorahigh
limit.Thesafetyloopmustbecomplete,andcannotbereconfigured.Thewiringofthesafety
loopisshownbelow:
Ifanerrorcode21isencountered,checkthefollowing:
1. TheburnerflangeswitchwiredbetweenterminalsX303.1andX303.2.Thereshouldbe
120VAConterminalX303.1atalltimes.Ifaburnerflangeswitchisnotpresent,ajumper
mustbeplacedbetweenterminalsX303.1andX303.2.
2. Operatingswitchesinthesafetyloop.Operating(cycling)switchesshouldnotbewired
intothesafetyloop.Ifacyclingswitchisplacedinthisloopanditcyclesoff,theLMV5will
lockout.Thecyclingswitchshouldberelocatedinserieswiththeburneron/offswitch
wiredtoX503.1:
IftheLMV5isinanyexternalloadcontrollermode(ExtLC…),thisisusedtocyclethe
burneronandoff.
IftheLMV5isinanyinternalloadcontrollermode(IntLC…),thenacyclingswitch
maynotbenecessary,sincethisisdoneautomaticallyintheLMV5usingparameters
SD_ModOnandSD_ModOff.
3. ThesafetyloopbetweenterminalsX304.1andX304.2
.Thereshouldbe120VACon
terminalX304.1atalltimes.Ifthereisnot,thenoneormoreofthedeviceswiredintothe
safetyloopareopen.Checkeachdevicewiredintothesafetylooptofindwhichoneis
open.