LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page11 Section7
LMV5WillNotStart(StaysinPhase12)
1. EnsurethattheLMV5isinautomaticmodethroughthefollowingmenupath:
ManualOperation>Autom/Manual/Off=Automatic
2. The burner will not start if the safety loop is open.Verify that there is 120 VAC on both
terminalsX303.1andX304.1.
3. Verifythatthereis120VACatburnerswitchinputterminalX503.1.
4. VerifythattheLMV5isnotinalarm.Ifso,correcttheissuecausingthealarmandresetthe
fault.
5. Verifythatignitionpositionsaredefinedforallactivatedactuators,includingtheVSD.This
canbedonethroughthefollowingmenupath:
Params&Display>RatioControl>Gas/OilSettings>SpecialPositions>IgnitionPos
6. Verifythattheactualvalueoftheboilerislessthantheswitchonthresholdoftheburner
(setpoint+SD_ModOn).