VSDWillNotOperate
IftheVSDwillnotoperatetheblower(blowerwillnotspin)whentheLMV52standardizationis
activated,checkthefollowing:
1. EnsurethattheVSDisactivatedthroughthefollowingmenupathintheLMV52:
Params&Display>RatioControl>Gas/OilSettings>VSD=activated
2. TheVSDcannotstandardizeifthesafetyloopisopen.Checkthatthesafetyloopisclosed
bymakingsurethereis120VAConterminalX303.1.Ifthereisnot,checkthelimitsinthe
safetyloopandtheburnerflangetoseewhichlimitisopen.
3. EnsurethattheLMV52isnotinalarm.Ifso,resetthefaultandattempttostandardize
again.
4. Verifythatthe0/420mAsignalandtherun/stopcontactwiredbetweentheVSDandthe
LMV52arewiredcorrectly.SeeSection2formoreinformationonwiring.
5. VerifythatthethreephasemotorwiringbetweentheVSDandthemotoriscorrect.
6. VerifythattheVSDissetupproperlyforthemotoritisdriving.Specifically,checkthe
following:
TheVSDshouldbespannedsothat0/4mAequals0Hzand20mA=62Hz(ona60Hz
gridfrequency).SeeSection5formoreinformation.
TheVSDisinremotemodesothatitlooksfora0/420mAsignalandarun/stop
contact.Closingtherun/stopcontactshouldcausetheVSDtooperatethemotor.
7. Disconnecttheanalogsignalandrun/stopcontactwiresbetweentheVSDandtheLMV52.
Useahandheld0/420mAsourceandatoggleswitchtoverifythattheVSDrespondstoa
contactclosureandavarying0/420mAsignal.
IftheVSDdoesnotrespond,correcttheconfigurationoftheVSD.
IftheVSDrespondstothecontactclosureandthevarying0/420mAsignal,
thengotothenextstep.
8. WiththewiresbetweentheLMV52andVSDstilldisconnected,useamultimetertoverify
thattheLMV52outputsabout19.5mAduringthestandardization(seenotebelow).Also
verifythattherun/stopcontactintheLMV52closesandremainsclosedduringthe
standardization.