EasyManua.ls Logo

Siemens LMV52.240B1 - Example: Temperature Transmitter Wired to Terminal X61

Siemens LMV52.240B1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Instructions LMV Series
Document No. LV5-800
0
Appendix A Page 34 SCC Inc.
Remote Setpoint (continued)
Example: Temperature Transmitter Wired to Terminal X
61
LC_OptgMode = IntLC X62
Ext Inp X62 U/I = 4..20 mA
MRange TempSens = 300 °F
Desired remote setpoint range = 200-240 °F
A 4-20 mA signal on terminal X62 scales the setpoint from 32-300 °F. Parameters “Ext
MinSetpoint” and “Ext MaxSetpoint” need to be utilized to get the appropriate setpoint range.
 =
200℉ 32℉
302℉ 32℉
=
168
270
= 62%
 =
240℉ 32℉
302℉ 32℉
=
208
270
= 77%
With these parameters set, the f
ollowing input signals will scale the setpoint accordingly:
4 – 13.9 mA = 200 °F (limited by “Ext MinSetpoint”)
13.9 – 16.3 mA = 200 - 240 °F
16.3 - 20 mA = 240 °F (limited by “Ext MaxSetpoint”)