VFD Bypass (continued)
Dual Fuel Procedure
1. Wire the LMV52, V
FD, and motor contactors as shown in Figure 15.
Figure 15: Wiring for a Dual Fuel VFD Bypass
2. Ensure the VFD is activated on gas, and deactivated on oil. This can be done through
the following menu paths:
Params & Display > RatioControl > Gas Settings > VSD = activated
Params & Display > RatioControl > Oil Settings > VSD = deactivated
3. Ensure the LMV52 is not set up for continuous purge. This can be done through the
following menu path:
Params & Display > BurnerControl > Configuration > ConfigGeneral >
ContinuousPurge = deactivated