EasyManua.ls Logo

Siemens LOGO! 24RC - Page 199

Siemens LOGO! 24RC
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
191
LOGO! Manual
A5E00067781 01
LOGO! 230RCL
LOGO! 230RCLB11
LOGO! 230RC
LOGO! 230RCo
Delay time at
0 after 1 Typically 50 ms Typically 50 ms
1 after 0
yy
Typically 50 ms
yy
Typically 50 ms
Line length (unshielded) 100 m 100 m
Digital outputs
Number 4 8
Output type Relay outputs Relay outputs
Electrical isolation Yes Yes
In groups of 1 2
Activation of digital input Yes Yes
Continuous current I
th
(per
connector)
Max. 10 A Max. 10 A
Incandescent lamp load
(25,000 switching cycles) at
230/240 V AC
115/120 V AC
1000 W
500 W
1000 W
500 W
Fluorescent tubes with electr.
control gear (25,000 switch-
ing cycles)
10 x 58 W (at
230/240 V AC)
10 x 58 W (at
230/240 V AC)
Fluorescent tubes, conven-
tionally compensated (25,000
switching cycles)
1 x 58 W (at
230/240 V AC)
1 x 58 W (at
230/240 V AC)
Fluorescent tubes, uncom-
pensated (25,000 switching
cycles)
10 x 58 W (at
230/240 V AC)
10 x 58 W (at
230/240 V AC)
Short circuit–proof cos 1 Power protection
B16
600A
Power protection
B16
600A
Short–circuit proof cos 0.5 to
0.7
Power protection
B16
900A
Power protection
B16
900A
Technical Specifications