EasyManua.ls Logo

Siemens LOGO! Series - Page 24

Siemens LOGO! Series
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Getting started with LOGO!
LOGO!
24 Manual, 04/2011, A5E03556174-01
Versions
The following LOGO! versions are available:
Symbol Designation Supply voltage Inputs Outputs Properties
LOGO! 12/24RCE 12/24V DC 8 digital
1)
4 relays
(10 A)
(0BA7)
LOGO! 230RCE 115 ... 240 V
AC/DC
8 digital 4 relays
(10A)
LOGO! 12/24RC 12/24 V DC 8 digital
1)
4 relays
(10 A)
LOGO! 24 24 V DC 8 digital
1)
4 solid state
24V / 0.3A
no clock
LOGO! 24C 24 V DC 8 digital
1)
4 solid state
24V / 0.3A
LOGO! 24RC
3)
24 V AC/
24 V DC
8 digital 4 relays
(10A)
LOGO! 230RC
2)
115 ... 240 V
AC/DC
8 digital 4 relays
(10A)
LOGO! 12/24RCo 12/24 V DC 8 digital
1)
4 relays
(10A)
no display unit
no keyboard
LOGO! 24o 24 V DC 8 digital
1)
4 solid state
24 V / 0.3A
no display unit
no keyboard
no clock
LOGO! 24Co 24 V DC 8 digital
1)
4 solid state
24 V / 0.3A
no display unit
no keyboard
LOGO! 24RCo
3)
24 V AC / 24 V DC 8 digital 4 relays
(10A)
no display unit
no keyboard
LOGO! 230RCo
2)
115 ... 240 V
AC/DC
8 digital 4 relays
(10A)
no display unit
no keyboard
1)
Of those can be used alternatively: 4 analog inputs (0 ... 10V) and 4 fast digital inputs.
2)
230 V AC versions: Two groups consisting of 4 inputs each. Each input within a group must be
connected to the same phase. It is possible to interconnect groups with a different phase.
3)
The digital inputs can be operated with P or N action.