International English 5. SYSTEM PARAMETERS
50 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
r0018 Firmware version
Displays the version number of the installed firmware.
-
-
[0]
-
1
2
CO: Actual frequency
r0021
-
-
[-]
Hz
2
13
CO: Actual output voltage
r0025
Displays the rms., voltage applied to the motor.
-
-
[-]
V
2
13
CO: Actual DC-link voltage
r0026
-
-
[-]
V
2
2
r0027
CO: Actual output current
Displays the rms. value of the motor current (A)
-
-
[-]
A
2
13
CO: Motor temperature (I
2
t)
r0034
Displays the calculated motor temperature as a percentage of the maximum allowed value.
Note:
A value of 100% means that the motor has reached its maximum allowed operating
temperature. When this occurs the inverter will attempt to reduce the motor loading as
defined by parameter P0610 (Level 3).
-
-
[-]
%
2
3
CO: Energy consumpt. Meter
r0039
Displays the electrical energy used by the drive since the display was last reset (see P0040)
Note:
Value will get reset when P3900=1 (during quick commissioning), or when P0970=1 (factory
reset) or by using P0040.
0
-
[0]
kW
2
2
Reset energy consumption meter
P0040
Resets energy consumption display to zero.
Possible Settings:
0 = No reset
1 = Reset r0039 to 0
Note:
Reset occurs when “P” is pressed.
0
1
[0]
-
2
2