Issue 01/06 Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
117
P1017[3] Fixed frequency mode - Bit 1 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1017 defines the mode of selection
Bit 1.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P1017[0] : 1st. Command data set (CDS)
P1017[1] : 2nd. Command data set (CDS)
P1017[2] : 3rd. Command data set (CDS)
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
P1018[3] Fixed frequency mode - Bit 2 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1018 defines the mode of selection
Bit 2.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P1018[0] : 1st. Command data set (CDS)
P1018[1] : 2nd. Command data set (CDS)
P1018[2] : 3rd. Command data set (CDS)
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
P1019[3] Fixed frequency mode - Bit 3 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm.: No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1019 defines the mode of selection
Bit 3.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P1019[0] : 1st. Command data set (CDS)
P1019[1] : 2nd. Command data set (CDS)
P1019[2] : 3rd. Command data set (CDS)
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
P1020[3] BI: Fixed freq. selection Bit 0 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 4000:0
Defines origin of fixed frequency selection.
Index:
P1020[0] : 1st. Command data set (CDS)
P1020[1] : 2nd. Command data set (CDS)
P1020[2] : 3rd. Command data set (CDS)
Common Settings:
P1020 = 722.0 ==> Digital input 1
P1021 = 722.1 ==> Digital input 2
P1022 = 722.2 ==> Digital input 3
P1023 = 722.3 ==> Digital input 4
P1026 = 722.4 ==> Digital input 5
P1028 = 722.5 ==> Digital input 6
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO)
Level
3
Level
3
Level
3
Level
3