Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
226 6SE6400-5BB00-0BP0
P2212[3] Fixed PID setpoint 12 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 110.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 12
Index:
P2212[0] : 1st. Drive data set (DDS)
P2212[1] : 2nd. Drive data set (DDS)
P2212[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2213[3] Fixed PID setpoint 13 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 120.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 13
Index:
P2213[0] : 1st. Drive data set (DDS)
P2213[1] : 2nd. Drive data set (DDS)
P2213[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2214[3] Fixed PID setpoint 14 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 130.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 14
Index:
P2214[0] : 1st. Drive data set (DDS)
P2214[1] : 2nd. Drive data set (DDS)
P2214[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2215[3] Fixed PID setpoint 15 Min: -200.00
CStat: CUT Datatype: Float Unit: % Def: 130.00
P-Group: TECH Active: Immediately QuickComm.: No Max: 200.00
Defines Fixed PID Setpoint 15
Index:
P2215[0] : 1st. Drive data set (DDS)
P2215[1] : 2nd. Drive data set (DDS)
P2215[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2216[3] Fixed PID setpoint mode - Bit 0 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm.: No Max: 3
Fixed frequencies for PID setpoint can be selected in three different modes. Parameter P2216 defines the
mode of selection Bit 0.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P2216[0] : 1st. Command data set (CDS)
P2216[1] : 2nd. Command data set (CDS)
P2216[2] : 3rd. Command data set (CDS)
P2217[3] Fixed PID setpoint mode - Bit 1 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm.: No Max: 3
BCD or direct selection Bit 1 for PID setpoint.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Index:
P2217[0] : 1st. Command data set (CDS)
P2217[1] : 2nd. Command data set (CDS)
P2217[2] : 3rd. Command data set (CDS)
Level
2
Level
2
Level
2
Level
2
Level
3
Level
3