EasyManua.ls Logo

Siemens MICROMASTER 440 - Fixed PID Setpoint, Binary Coded (P2216 - P2219 = 3) Diagram

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue 01/06 Function Diagrams
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
277
- 3310 -
Function diagram
87654321
3310_FPID.vsd
Internal Setpoint Source
MICROMASTER 440
16.01.2006 V2.1
Fixed PID setpoint, binary coded
0 0 0 1
0 1 0 1
0 1 1 0
1 1 1 1
0 0 0 0
Fixed PID setp. 5
-200.00 ... 200.00 [%]
P2205.D (40.00)
Fixed PID setp. 6
-200.00 ... 200.00 [%]
P2206.D (50.00)
Fixed PID setp. 15
-200.00 ... 200.00 [%]
P2215.D (130.00)
r2224
CO: Fixed.PID setp
Fixed PID setp. 1
-200.00 ... 200.00 [%]
P2201.D (0.00)
.
.
.
.
.
.
1
.
.
.
.
.
.
Fixed PID setp. 4
-200.00 ... 200.00 [%]
P2204.D (30.00)
0 1 0 0
(0:0)
BI:PID setp->Bit 0
P2220.C
0
1,2
3
Fix.PID setp.Bit 0
1 ... 3
P2216.C (1)
0
1,2
3
(0:0)
BI:PID setp->Bit 1
P2221.C
Fix.PID setp.Bit 1
1 ... 3
P2217.C (1)
0
1,2
3
(0:0)
BI:PID setp->Bit 2
P2222.C
Fix.PID setp.Bit 2
1 ... 3
P2218.C (1)
0
1,2
3
(722:3)
BI:PID setp->Bit 3
P2223.C
Fix.PID setp.Bit 3
1 ... 3
P2219.C (1)
(P2216 - P2219 = 3)
OFF1
ON/OFF1
1
0
0
1: If all FF mode selections equal 3
(P2216 = P2217 = P2218 = P2219 = 3)
0: For all other cases
www . ElectricalPartManuals . com