EasyManua.ls Logo

Siemens MICROMASTER 440 - Motor Parameters

Siemens MICROMASTER 440
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Description Issue 01/06
MICROMASTER 440 Parameter List
50 6SE6400-5BB00-0BP0
3.4 Motor parameters
P0300[3] Select motor type Min: 1
CStat: C Datatype: U16 Unit: - Def: 1
P-Group: MOTOR Active: first confirm QuickComm.: Yes Max: 2
Selects motor type.
This parameter is required during commissioning to select motor type and optimize inverter performance.
Most motors are asynchronous; if in doubt, use the formula below.
P0311
60
P0310 x â‹…=
Synchronous motorx = 1, 2, ..., n :
x ≠ 1, 2, ..., n : Asynchronous motor
If the result is a whole number, the motor is synchronous.
Possible Settings:
1 Asynchronous rotational motor
2 Synchronous rotational motor
Index:
P0300[0] : 1st. Drive data set (DDS)
P0300[1] : 2nd. Drive data set (DDS)
P0300[2] : 3rd. Drive data set (DDS)
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
If synchronous motor is selected, the following functions are not available:
- P0308 Power factor
- P0309 Motor efficiency
- P0346 Magnetization time
- P0347 Demagnetization time
- P1335 Slip compensation
- P1336 Slip limit
- P0320 Motor magnetizing current
- P0330 Rated motor slip
- P0331 Rated magnetization current
- P0332 Rated power factor
- P0384 Rotor time constant
- P1200, P1202, P1203 Flying start
- P1230, P1232, P1233 DC braking
Level
2
www . ElectricalPartManuals . com