Issue 08/03
MICROMASTER 440
6SE6400-5GA00-0BP0
Quick Start Guide 47
Parameter
Number
Parameter Description Suggested
Setting
User
Setting
P0205
Set Inverter Application
0 Constant torque (e.g. compressors, conveyors)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter switches you between the Constant
Torque and Variable Torque rating on an MM440 drive –
where applicable.
This parameter is only usable for 3ph input inverters
Frame Size C and larger. On smaller units it is not
changeable.
0
P0300[0]
Select Motor Type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control
types (P1300 < 20) are permitted.
Some features are not available if you have a
synchronous motor – please refer to Parameter List
document for complete information
1
P0304[0]
Enter Rated Motor Voltage
(enter value from motor name plate)
NOTE
The rated motor voltage on the name plate must be
checked, regarding the Wye(star)/delta circuit
configuration to ensure that it matches with the circuit
connection configured at the motor terminal board.
From
Name
Plate
P0305[0]
Enter Rated Motor Current
(enter value from motor name plate)
From
Name
Plate
P0307[0]
Enter Rated Motor Power
(enter value from motor name plate)
If P0100 = 0 or 2, the entry is in kW and for P0100 = 1, in
hp.
From
Name
Plate
P0308[0]
Enter Rated Motor CosPhi (Power Factor)
(enter value from motor name plate)
If the setting is 0, the value is automatically calculated.
NOTE
You will not see this parameter on your BOP if P0100=1
This is NOT the service factor (cos Ï• value is always<1)
From
Name
Plate