Operation
8.6 Modes of Operation
BW500 and BW500/L
100 Operating Instructions, 12/2016, A5E33482052-AD
8.6
Modes of Operation
RUN
is the normal or reference mode of operation. It continuously processes the load and speed
signals from the belt scale to produce internal load, speed and rate signals, which are in turn
used as the basis for totalization, mA output, relay control, and communication data. The
RUN
display is programmed (P081) to scroll through rate, totalization (P647), load and speed; either
manually by pressing the enter key, or automatically.
Rate
Total 1
Rate
Total 2
Load
Speed
If the BW500 is programmed for batch control, the batch display is added to the display scroll.
Refer to Batch Control (Page 176) for more information.
From the
RUN
mode, access to the
PROGRAM
mode, and zero and span calibration is made.
The
PROGRAM
mode allows viewing and, with security permission (P000), editing parameter
values. During
PROGRAM
,
RUN
mode functions are still active, that is.: rate, relay, mA output
and totalization.
If the
PROGRAM
mode is left idle for a period of ten minutes, it automatically reverts to
RUN
mode.
Zero and span calibrations effectively halt the
RUN
mode while they are in progress. During this
time, totalization ceases, and all mA outputs, except for PID, fall to zero.
8.7
Damping
Damping (P080) provides control over the speed at which the displayed readings and output
functions respond to changes in their respective input function: load, speed and the internal rate
signals. Changes in the displayed rate of material flow, material loading and belt speed are
controlled by the damping. Relay alarm functions based on input functions of rate, load and
speed, respond to the damped value.
Damping consists of a first order filter applied to the signal (reading or output value).
If mA damping (P220) is enabled (value other than 0), then the damping (P080) as it pertains to
the mA function is overridden, and responds independently at the specified mA output damping
rate (P220).
Note
Damping (P080 or P220) is not applicable to the mA output when programmed for PID
fu
nction (P201 = 4).