Communications
11.3 Configuring Communication Ports
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
131
Note
Applicable only to ports programmed for printer
communication (P770).
Sets the data message to be delivered via the selected port, ports 1 to 3 (P781-01 to -03). All
messages and printouts include time and date
2)
.
0
f
= no message
1 = rate
2 = total
1)
3 = load
4 = speed
5 = rate, total
1)
, load and speed
6 = rate and total
1)
7 = batching
2)
8 = rate and speed
9 = quick start parameters (P001 – P017)
10 = all parameters
1)
Totalizer 1 and/or 2 as set by P647, Totalizer Display.
2)
Not available with BW500/L
P799 Communications Control
Assigns programming control either locally through the keypad or Dolphin Plus (P770 = 1), or
remotely through Modbus protocol (P770 = 2 or 3) or SmartLinx.
:
0 = local
1 = remote
When a SmartLinx card is installed and P799 = 1, the parameters that the SmarlLinx card is
writing to the BW500 and BW500/L will be continuously updated. Therefore, if you connect
a SmartLinx card to the BW500 and BW500/L, set P799 = 1 and not write anything to the
SmarLinx card, your setpoints will be zero.