EasyManua.ls Logo

Siemens Milltronics BW500/L - Page 148

Siemens Milltronics BW500/L
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
11.5 Modbus RTU/ASCII Protocol
BW500 and BW500/L
146 Operating Instructions, 12/2016, A5E33482052-AD
Parameter Values
Bit Mapped bits are packed into registers in groups of 16 bits (1 word). In this manual we
number the bits from 1 to 16, with bit 1 being the least significant bit and bit 16 referring to the
most significant bit.
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
MSB
LSB
Large numbers are put into unsigned 32 bit integers with a fixed decimal place of three. For
example, a value of ‘7345’ represents a value in the BW500 ‘7.345’. The default word order is
that the first word is the most significant word (MSW) and the second word (register) is the least
significant word (LSW).
For example, if we read R41,431 as a 32-bit, the 32 bits would look like the following:
R41,431
R41,432
16
MSB
1
16
LSB
1
32 32-bit integer value (UNINT32) 1
The whole is read as a 32-bit integer. The most significant byte (MSB) and least significant byte
(LSB) can be reversed to accommodate some Modbus drivers.
Text Messages
If a Siemens Milltronics device parameter returns a text message, that message is converted to
a number and provided in the register. The numbers are shown in the table below:
Number
Text Message as Displayed on LCD
22222
invalid value
30000
off
30001
on
30002
= = = =
30003
(parameter does not exist)
30004
err
30005
err1
30006
open
30007
shrt
30008
pass
30009
fail
30010
hold
30012
hi
30013
de
30014
en
-32768
value is less than -20,000
32767
value is greater than 20,000

Table of Contents

Related product manuals