Parameters
12.1 Start Up (P001 to P017)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
155
Enter the current time in
hh-mm-ss
24 hour format.
hh=hour
mm=minute
ss=second
Note
Not available with BW500/L.
Specifies the design rate of material flow for the belt scale (
f
= 0.00).
Enter the design rate in the units selected (P005).
Specifies the design speed for the conveyor belt (
f
= 0.00)
Speed units are:
feet/min if the imperial system of measurement has been selected, P004 = 1
metres/s if the metric system of measurement has been selected, P004 = 2
Set the speed constant for the speed sensor selected (P015-01 or 02)
1)
.
1)
Index 02 is not available with BW500/L
The value in P015-01 is used with the speed sensor frequency, to calculate the actual belt speed
(f = 0.000).
The value in P015-02 is used for differential speed detection
2)
.
2)
Not available with BW500/L
Note
Entry: If speed input is wired for constant speed (terminals 17/18 jumpered), value defaults
to jumpered, and the second speed sensor is ignored.
If the speed input is connected to a speed sensor, press ENTER . P015 automatically jumps to
P690. Refer to P690 (Page 183) for speed constant entry.