Parameters
12.2 Relay/Alarm Function (P100 - P117)
BW500 and BW500/L
158 Operating Instructions, 12/2016, A5E33482052-AD
The
displays are scrolled either manually by pressing ALT DISP if the scroll mode is set to
off, or automatically if the mode is set to on.
0
f
= OFF
1 = ON
Relay/Alarm Function (P100 - P117)
Note
BW500 has 5 programmable relays and BW500/L has 2
These parameters are specific to the use of the relay/alarm function. Refer to Operation
(Page 97)
.
Sets the relay function for the relay selected; BW500: relays 1 to 5 (P100 -01 to -05), BW500/L:
relays 1 and 2 (P100 - 01, 02)
To reset the Diagnostics relay, the BW500 and BW500/L must be cycled between
PROGRAM and RUN mode
To reset the Batch relays, the Batch totalizer must be reset.
0 = OFF
f
1 = rate
2 = load
3 = speed
4 = diagnostic
5 = PID-01 setpoint deviation
1)2)
6 = PID-02 setpoint deviation
1)2)
7 = pre-warn
1)3)
8 = setpoint
1)3)
9 = online calibration
1)4)
10 = differential speed detection
1)5)
11 = certification rate alarm (high alarm preset to 100%, low alarm preset to 20 %)
6)
1)
Not available with BW500/L
2)
Valid only if PID system (P400) is enabled
3)
Valid only if batch function (P560) is enabled
4)
Valid only if online calibration (P355) is enabled
5)
Valid only if Aux. input (P270) = 16 (differential speed detection)
6)
When selected parameters P101 and P102 are locked