Parameters
12.3 mA I/O Parameters (P200 - P220)
BW500 and BW500/L
162 Operating Instructions, 12/2016, A5E33482052-AD
Sets the minimum mA limit for the output selected, outputs 1 to 3 (P212 - 01 to - 03)
2)
. The limit
sets the lower mA range (0 or 4 mA) to a minimum output value (
f
= 3.80).
Enter limit value, range 0 - 22
2)
BW500/L has one output, parameters will not present multiple indexes.
Sets the maximum mA limit for the output selected, outputs 1 to 3 (P213 - 01 to - 03)
2)
. The limit
sets the upper mA range (20 mA) to a maximum output value (
f
= 22.00).
Enter limit value, range 0 - 22
2)
BW500/L has one output, parameters will not present multiple indexes.
Trims the 4 mA output level for the output selected, outputs 1 to 3 (P214 - 01 to – 03)
1)
. The trim
adjust the output to agree with a milliameter or other external mA input device.
Scroll the trim value up or down
1)
BW500/L has one output, parameters will not present multiple indexes.
Trims the 20 mA output level for the output selected, outputs 1 to 3 (P215 - 01 to - 03)
1)
. The trim
adjust the output to agree with a milliammeter or other external mA input device.
Scroll the trim value up or down
1)
BW500/L has one output, parameters will not present multiple indexes.
Sets the damping for the output selected, outputs 1 to 3 (P220 - 01 to - 03)
1)
. Damping sets the
speed at which the mA output reacts to change. The greater the damping value, the slower the
response. If the value is 0, the mA output assumes the damping set in P080 (
f
= 0.00).
Enter the damping value, range 0.001 – 999
1)
BW500/L has one output, parameters will not present multiple indexes.