12.3 mA I/O Parameters (P200 - P220)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
163
12.3.9
P250 mA input range
Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to - 02).
Entry
:
1 = 0 - 20 mA
2 = 4 - 20 mA
f
Note
Not available with BW500/L.
12.3.10
P255 mA Input Function
Assigns the mA input function for the input selected, inputs 1 to 2 (P250 - 01 to - 02)
0 = OFF
f
1 = PID setpoint
2 = PID process variable
3 = Online calibration
1)
4 = Moisture compensation
5 = Incline compensation
Note
Not available with BW500/L.
1)
Valid only if Online Calibration is turned on, (P355 = 1).
12.3.11
P261 4 mA Input Trim
Trims the 4 mA input level for the input selected, inputs 1 to 2 (P250 - 01 to - 02). The trim
adjusts the input to agree with an external 4 mA source.
Follow the BW500 online instructions to trim the input
Note
Not available with BW500/L.