Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to - 02).
:
1 = 0 - 20 mA
2 = 4 - 20 mA
f
Note
Not available with BW500/L.
Assigns the mA input function for the input selected, inputs 1 to 2 (P250 - 01 to - 02)
0 = OFF
f
1 = PID setpoint
2 = PID process variable
3 = Online calibration
1)
4 = Moisture compensation
5 = Incline compensation
Note
Not available with BW500/L.
1)
Valid only if Online Calibration is turned on, (P355 = 1).
Trims the 4 mA input level for the input selected, inputs 1 to 2 (P250 - 01 to - 02). The trim
adjusts the input to agree with an external 4 mA source.
Follow the BW500 online instructions to trim the input
Note
Not available with BW500/L.