12.4 Calibration Parameters (P295 P360)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
167
3)
Enter 1 (existing ALT_DSP) to reject the new online calibration span.
multispan selection
Auxiliary Input
auxiliary input 2
auxiliary input 3
1
2
3
4
5
6
7
8
If an attempt is made to select a multispan that has not been zero and span calibrated, the
selection request is ignored.
Note
When performing a remote span, it will first perform a zero, then it will ask you to set up
span test. Once loading is within +/- 2% of the design test weight, it will perform the span.
For the print command to work, the BW500 and BW500/L must be in RUN mode.
12.4
Calibration Parameters (P295 P360)
12.4.1
P295 Load Cell Balancing
Initiates an electronic balancing of the load cell input signals. Balancing is required for belt scale
models of two, four, or six load cell design.
Refer to Start Up (Page 47) for requirements and execution.
12.4.2
P341 Days Of Service
The cumulative days that the application device has been in service. The time is recorded once
daily in a non-resetable counter. Periods of less than 24 hours. are not recorded, nor
accumulated (
f
= 0).