Parameters
12.8 Batch Control (P560 P568)
BW500 and BW500/L
176 Operating Instructions, 12/2016, A5E33482052-AD
12.7.11
P416 External Setpoint
Displays the external setpoint (P416-01 / 02), in engineering units, for the corresponding PID
system (1 or 2). For the external process variable, the setpoint is shown is %.
If the setpoint is external (P414 = 1 or 2), then this parameter displays the setpoint value that is
being input, either mA input 1 or 2.
12.7.12
P418 Remote Setpoint Ratio
Sets the remote setpoint ratio (P418 01/02) for the corresponding PID system (1 or 2) when
P414 = 1 or 2 (
f
= 100).
The remote setpoint ratio scales remote setpoint input by the set percentage. A value of 100
means that the setpoint is 100% of the mA input.
12.7.13
P419 PID Freeze Option
Note
If the input speed frequency drops below 5 Hz, the PID control output freezes at its current
value.
Enables or disables the PID freeze option described in the note above.
Entry:
0 = OFF
1 = ON
f
12.8
Batch Control (P560 P568)
The following parameters are specific to the use of the BW500 as a batch controller. P564-P568
is accessible only when Count Up (1) is selected.
Note
Not available with the BW500/L
12.8.1
P560 Batch Mode Control
Enables the batch control function.
Batch control is count up.
Entry:
0 = OFF
f
1 = count up