12.9 Totalization (P619 - P648)
BW500 and BW500/L
180 Operating Instructions, 12/2016, A5E33482052-AD
12.9.5
P634 Communication Totalizer Resolution
Used to set the number of fixed decimal places for Total 1 and Total 2 for SmartLinx or Modbus
communication.
Entry:
P634 Index
Description
Value
# of decimal places
Primary Index 1 Total 1 for SmartLinx
communication
3
f
3
2
2
1
1
0
0
Primary Index 2 Total 2 for SmartLinx
communication
3
f
3
2
2
1
1
0
0
With 3 decimal places set, the largest readable value is 2, 147, 483.638. With 2 decimal places
set, the largest readable value is 21, 474, 836.38. With 1 or 0 decimal places set, the largest
readable value is 100, 000, 000.
Note
This parameter is only relevant if viewing the totalizer value using remote communications,
such as SmartLinx or Modbus.
12.9.6
P635 Verification Totalizer
Enables a dedicated internal totalizer that totals the amount of material conveyed during a zero
or span verification. It is used to verify the accuracy of the scale.
If a printer is connected to a port and the required programming is in order, a printout of the
activity is automatically done on completion of the verification process.
Note
Date and time are not av
ailable with the BW500/L