Parameters
12.9 Totalization (P619 - P648)
BW500 and BW500/L
182 Operating Instructions, 12/2016, A5E33482052-AD
P643 External Contact Closure
Sets the duration of the contact closure, in ms, for the external totalizer selected, totalizers 1 and
2 (P643-01 or -02) (
f
= 30)
Permissible values are in 10 ms increments from 0. The value is automatically calculated upon
entry of P011 (design rate) and P638 (totalizer 1 resolution, external) so that the duration of
contact closure allows the transistor switch response to track the total, up to 150% of the design
rate. The value can be changed to suit specific contact closure requirements, such as in the
case of programmable logic controllers.
If the duration selected causes the totalizer to lag behind the count rate, the next possible
duration is automatically entered.
External Totalizer output frequency must not exceed 13.33 Hz at 150% of design rate.
Selects the totalizer combination to be displayed, either manually through the scroll display key
or automatically by control of the display mode (P081).
1 = totalizer 1
f
2 = totalizer 2
3 = totalizer 1 and 2
P648 Totalizer Reset, Internal
Manual reset of the selected internal totalizer when the entry is made (
f
= 0).
0 = no reset
1 = reset totalizer 2
2 = reset totalizers 1 and 2
Resetting the internal totalizers 1 and 2 resets the internal registers for external totalizers 1 and
2.