Parameters
12.10 ECal Parameters (P693 P698)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
185
12.10.3
P695 ECal Load Cell Sensitivity
Enters the load cell’s sensitivity for the selected cell (
f
= 1.0).
-01 = load cell A
-02 = load cell B
-03 = load cell C
2)
-04 = load cell D
2)
Enter the value in mV/V obtained from load cell nameplate.
2)
Not available with BW500/L
12.10.4
P696 ECal Load Cell Excitation
Determines the excitation applied to the load cells.
Nominally this value is 10 V. However, a measurement of the voltage at the load cell provides
the most accurate entry.
Enter the load cell excitation in V DC.
12.10.5
P697 ECal Idler Spacing
Enters the measured distance between the weighing idlers. Refer to the associated belt scale
instruction manual (
f
= 1.0).
Distance units are:
feet: if the imperial system of measurement has been selected, P004 = 1
metres: if the metric system of measurement has been selected, P004 = 2
Enter the distance to three decimal points.
12.10.6
P698 ECal Conveyor Inclination
Enters the inclination or declination angle of the conveyor at the point where the belt scale is
installed (
f
= 0.0000).