5.5 Speed
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
35
Cable shields must connect to ground only through the BW500 or BW500/L Motherboard
(TB15). They should not be grounded to the LVDT Conditioner Card enclosure or any other
location.
* Where separation between the BW500 or BW500/L and LVDT conditioner exceeds 150 m
(500 ft):
1. remove jumpers from BW500 and BW500/L terminal 11/12 and 13/14
2. run additional conductors from:
BW500 terminal 12 to integrator terminal block '+EXC'
BW500 terminal 13 to integrator terminal block '-EXC'
Note
LCA (Terminal 2) is jumpered to SHLD (Terminal 5), which internally connects to the load
cell circuit common.
Do not connect to the Speed Sensor (Terminal 17) common, it is isolated from the load
cell circuitry.
5.5
Speed
5.5.1
Constant Speed (No Sensor)
If a speed sensor is not used, a jumper or
contact closure must be co
nnected across
BW500 and BW500/L terminals 17 / 18 when
the conveyor is running. If a speed sensor is
used, ensure that the jumper is removed.
Note:
With contact closed or jumpered when
the conveyor is idle, the integrator will conti
n-
ue totalizing.
Speed sensor