Start Up
6.4 Load Cell Balancing
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
65
Calibration Complete Deviation
Press ENTER to accept value:
0.00
● the deviation from the previous span. For an initial span, there is no previous span count;
hence the deviation is 0.
● For example: the new span count, if accepted.
Press the following key:
Span Calibration. Current Span
Setup test. Press ENTER to Start
36790
For example: the current span count.
Accepting the Span returns to start of Span. A new Span can be performed, or enter
mode.
If calibrating with a test weight or test chain, remove it from the scale and store in a secure place
before returning to
mode.
Note
The moisture meter is ig
nored during calibration. If the Inclinometer is used, then calibration
is adjusted based on incline angle.
Proper programming and successful zero and span calibration allow entry into the
mode.
Otherwise, entry is denied and the first missing item of programming or calibration is displayed.
Press the following key:
Rate
0.00 t/h
For example: if there is no material on the belt and the conveyor is running. The current rate is 0 and
no material has been totalized.
Once the initial programming is complete and the BW500 and BW500/L is operating in the
mode, you may now put the belt conveyor into normal service. The BW500 is functioning under
its initial program and calibration, reporting rate of material flow and totalizing.