Operating the shutters
139-2021.9 / 07 NXAIR M 149
Closing the shutter to the connection compartment (lower shutter)
NOTICE
Maloperation
Risk of damaging safety-relevant parts.
Remove the padlock before inserting the withdrawable part.
Push the handle of the slip-on lever slightly to the left (to release the latch) and let it slip
upwards. The shutter closes.
Remove the slip-on lever.
Remove the padlock from the left side in the switching-device compartment.
The shutter to the connection compartment is closed.