Service information
244 NXAIR M 139-2021.9 / 07
25.5 Lubricants to be used
CAUTION
Injury due to incorrect application
Incorrect application of the lubricants can cause injuries of the sense organs or the
hands.
Observe the safety instructions in the safety data sheets of the lubricant
suppliers.
Put on personal protective equipment.
Component
Lubricant
Supplier
Shutter guiding linkage (1)
WD-40 waterproof spray oil
Hardware store
Guide rails (2)
ISOFLEX TOPAS L 32
(Order No.: 3AX1133-3E 1 kg)
www.klueber.com
Fixed contacts of feeder
earthing switch (3)
MOLYKOTE® LONGTERM 2 PLUS
EXTREME PRESSURE BEARING
GREASE
(Order No.: 8BX1022 1 kg)
www.dowcorning.com
Main fixed contacts of
bushings (4)
Fig. 400: Circuit-breaker, disconnecting and
metering panels
Fig. 401: Circuit-breaker panel with HV HRC fuses
(1) Shutter guiding linkage
(2) Guide rail
(3) Fixed contacts of the feeder
earthing switch
(4) Fixed contacts of the bushings