Operating the metering panel
139-2021.9 / 07 NXAIR M 81
Fig. 129: Removing the plastic tube
To remove the fuse holder (3), undo the two steel bolts M6x20 with the steel washers 6 (4)
completely, and keep for later use.
Remove the plastic tube, and keep for later use.
Fig. 130: Removing the fuse holder
Fig. 131: Fuse holder
Loosen the protection fuse-link by turning back and forth, and pull it out of the voltage
transformer housing with mounted contact cap.
Detach the contact cap from the protection fuse-link.
Fig. 132: Detaching the fuse-link
Fig. 133: Removing the
fuse-link
Fig. 134: Detaching the
contact cap
4
3
2
1