7.5.11 Function Block DO
Function Block DO (Digital Output)
Class Sl
ot
Index
abs
Ind
ex
rel
Elem
ent
Default
Value
Object Parameter description Data Type Num
ber
Store
(acc. to
profile)
cy
cli
c
re
ad
wri
te
BLOCK
5 16 0 BLOCK_OBJECT Block characteristic ds32 1 C x
1 250 Reserved 250 = not used
2 2 Block Object Block-Typ (Function)
3 2 Parent Class Parent class: 01 = Input
4 2 Class 01 = Analog Input
5 0 DD-Reference reserved
6 0 DD-Revision reserved
7 0x4002 Profile PA-profil-number assigned by PNO for
PROFIBUS - PA = 64
8 0x0300 Profile Revision Profile 3.0
9 0 Execution Time f0r future use
10 45 NumberOfParameters number of parameters
11 0x054b Address of VIEW 1 Index of view 1
12 1 Number of View Lists Number of views
STD 17 1 0 ST_REV Identification / device / statistic rev.-no. /
Function Block: counter which is incremented
at any change of configuration parameters
unsigned16 1 N x
STD 18 2 TAG_DESC Unique tag in the system which can be used
by the user
visible_string 32 S x x
STD 19 3 0 STRATEGY Strategy unsigned16 1 S x x
STD 20 4 0 ALERT_KEY User can write value for alert handling unsigned8 1 S x x
STD 21 5 0x08 TARGET_MODE Target mode of block = Auto unsigned8 1 S x x
STD 22 6 MODE_BLK Set block mode ds37 1 D x
1 0x08 Actual Actual mode
2 0x98 Permitted Permitted modes: Auto, O/S, MAN
3 0x08 Normal Set mode in normal operation
STD 23 7 ALARM_SUM Alarm status ds42 1 D x
1 0x0000 Current_Alarm Current Alarm
2 0x0000 Unacknowledged Not acknowledged
3 0x0000 Unreported Not reported
4 0x0000 Disabled Disabled
STD 24 8 BATCH Information for Batch-Process ds67 1 S x x
1 BATCH_ID
2 RUP
3 OPERATION
4 PHASE
MAND 25 9 SP_D ds34 1 D x x
0 Value
0x1B Status
O(A),
M(B)
26 10 OUT_D ds34 1 D x x
0 Value
0x4F Status
OPT 28 12 READBACK_D ds34 1 D x
0 Value
0x4F Status
O(A),
M(B)
30 14 RCAS_IN_D ds34 1 D x x
0 Value
0x1B Status
SPEC 0x0123 IN_CHANNEL Pointer for input (FEEDBACK) unsigned16 1 N
O(A),
M(B)
33 17 0x0122 CHANNEL Pointer for output (POSITIONING_VALUE) unsigned16 1 S x x
MAND 34 18 0 INVERT unsigned8 1 S x x
O(A),
M(B)
35 19 30.0 FSAVE_TIME float 1 S x x
O(A),
M(B)
36 20 1 FSAVE_TYPE unsigned8 1 S x x
O(A),
M(B)
37 21 0 FSAVE_VAL_D unsigned8 1 S x x
O(A),
M(B)
38 22 RCAS_OUT_D ds34 1 D x
0 Value