Perfect Harmony GENIII/e User’s Manual Hardware Components
A1A19000405A: Version 1.3 2-9
2
Table 2-2: GENIII Cell Specification Details
Table 2-3: GENIII/e Cell Specification Details
The individual output cells are located in the Cell Section. All cells are electrically and mechanically identical, so that
they may be interchanged. Each cell contains its own control boards, which communicate with the system through a
fiber optic link. This link is the only connection between the cells and the master control located in the Control
Section, thus each cell is isolated from the main control. Refer to Figure
2-7 for GENIII type cell. Refer to Figure 2-8
and Figure 2-9 for GENIII/e type cells.
Figure 2-7: Typical GEN III Cell
Output
Cells Per
Phase
Line-to-Line
Voltages(VAC)
Cells in Drive
(Without
Spares)
hp Range Available Cell Sizes
3 3,300 9 up to 1500 70A, 100A, 140A,200A, 260A
4 4,160 12 up to 2000 70A, 100A, 140A,200A, 260A
6 6,600 18 up to 3000 70A, 100A, 140A,200A, 260A
Output
Cells per
Phase
Line-to-Line
Voltages (VAC)
Cells in Drive
(without spares)
Hp Range Available Cell Sizes
2 2,300 6 up to 3000 315A, 375A, 500A, 660A
3 3,300 9 up to 4000 315A, 375A, 500A, 660A
4 4,160 12 up to 6000 315A, 375A, 500A, 660A
5 6,000 15 up to 8000 315A, 375A, 500A, 660A
6 6,600 18 up to 0000 315A, 375A, 500A, 660A