The Keypad and Display Interface Perfect Harmony GENIII/e User’s Manual
3-32 A1A19000405A: Version 1.3
s
s
ss
3
Table 3-16: Spinning Load Menu (2420)
Table 3-17: Conditional Timer Setup Menu (2490)
Parameter ID Units Default Min Max Description
Spinning load
mode
See Note below
2430 Off
Enable/Disable Spinning Load and set
the direction of frequency scans:
•Off
•Forward
•Reverse
•Both
Enable Spinning Load if the drive is
required to detect the speed of an
already spinning motor. Spinning Load
should be Enabled for Fast Bypass or
Synchronous Motor, and should be
disabled for OLTM.
Scan end
threshold
2440 % 20.0 1.0 50.0
Point where scan ends if motor flux is
above this level, as a percentage of
motor rated flux.
Current Level
Setpoint
2450 % 15.0 1.0 50.0
Sets the drive current level (I
d
), as a
percentage of motor rated current, used
during scanning.
Current ramp 2460 sec 0.01 0.00 5.00
Time to ramp drive current (I
d
)to
Current Level Setpoint.
Max current 2470 % 50.0 1.0 50.0
Sets the current trip level, as a
percentage of motor rated current, for
scanning. Use the default value of 50%.
Frequency scan
rate
2480 sec 3.00 0.00 5.00
Sets the time taken to scan from rated
speed to zero. The default value of 3.00
sec should be satisfactory for most
cases.
Parameter ID Units Default Min Max Description
Cond stop timer 2500 sec 0.8 0.0 999.9
Dwell time after stop is invoked. User
function defined. (Not currently imple-
mented)
Cond run timer 2510 sec 0.8 0.0 999.9
Dwell time after start is invoked. User
function defined. (Not currently
implemented)