Perfect Harmony GENIII/e User’s Manual The Keypad and Display Interface
A1A19000405A: Version 1.3 3-33
s
s
ss
3
Table 3-18: Cell Menu (2520)
Parameter ID Units Default Min Max Description
Installed cells/phase 2530 4 1 8 Installed cells per phase in the drive.
Min cells/phase count
(n/3)
2540 4 1 8 Minimum cells per phase count.
Cell voltage 2550 Vrms 630
Sets the value of the cell rated
voltage:
•460V
•630V
•690V
Thermistor warn level 2560 % 20.0 5.0 70.0
Sets the level at which a temperature
alarm is generated.
Contactor settling time 2570 msec 250.0 0.0 1000.0
Time taken by bypass contactors to
change state. Use 100ms for small
contactors and 250ms for larger
ones.
Max back EMF decay
time
2580 sec 7.0 0.0 10.0
Sets the maximum time that the
control waits for the motor voltage
to decay while attempting a fast
bypass.
Once cell fault(s) occurs, the drive
may not be able to support actual
motor voltage. If the motor voltage
does not decay below the max drive
voltage capability (with the faulted
cell(s)) within the time set by this
parameter, the drive issues a fault.
Bypass Type 2590 Mech
Designates the type of bypass in the
drive:
Mechanical
None
Fast bypass 2600 Disable
This parameter enables or disables
fast cell bypass. Disabling fast
bypass with mechanical contactors
will still provide manual bypass after
a manual reset.
Display Cell Status 2610 Function
Displays cell status:
A = active,
B = bypassed,
•F = faulted.