Perfect Harmony GENIII/e User’s Manual The Keypad and Display Interface
A1A19000405A: Version 1.3 3-45
3
Table 3-34: Analog Input #1 Menu (4100)
Table 3-35: Analog Input #2 Menu (4170)
Parameter ID Units Default Min Max Description
Source 4105 Off
This parameter sets the input source for
analog input #1
•Off
• Ext 1-24
Type 4110 4 – 20mA
This parameter sets the operational
mode for analog input 1.
•0 - 20mA
•4 - 20mA
•0 - 10V
Min input 4120 % 0.0 0.0 200.0 Minimum Analog input
Max input 4130 % 100.0 0.0 200.0 Maximum Analog input
Loss point threshold 4140 % 15.0 0.0 100.0
Threshold where loss of signal action is
activated.
Loss of signal action 4150 Preset
Select loss of signal action.
•Preset
• Maintain
•Stop
Loss of signal
setpoint
4160 % 20.0 0.0 200.0 Loss of signal preset speed.
Parameter ID Units Default Min Max Description
Source 4175 Off
This parameter sets the input source for
analog input #2.
•Off
•Ext 1-3
Type 4180 4 – 20mA
This parameter sets the operational
mode for analog input 2.
• 0 – 20mA
• 4 – 20mA
• 0 – 10V
Min input 4190 % 0.0 0.0 200.0 Minimum Analog input
Max input 4200 % 100.0 0.0 200.0 Maximum Analog input
Loss point threshold 4210 % 15.0 0.0 100.0
Threshold where loss of signal action is
activated.