The Keypad and Display Interface Perfect Harmony GENIII/e User’s Manual
3-46 A1A19000405A: Version 1.3
3
Table 3-36: Analog Input #3 Menu (4232)
Loss of signal action 4220 Preset
Select loss of signal action.
•Preset
•Maintain
•Stop
Loss of signal set-
point
4230 % 20.0 0.0 200.0 Loss of signal preset speed.
Parameter ID Units Default Min Max Description
Source 4233 Off
This parameter sets the input source for
analog input #1.
•Off
• Ext 1-24
Type 4234 4 – 20mA
This parameter sets the operational
mode for analog input 1.
• 0 – 20mA
• 4 – 20mA
• 0 – 10V
Min input 4235 % 0.0 0.0 200.0 Minimum Analog input
Max input 4236 % 100.0 0.0 200.0 Maximum Analog input
Loss point threshold 4237 % 15.0 0.0 100.0
Threshold where loss of signal action is
activated.
Loss of signal action 4238 Preset
Select loss of signal action.
•Preset
• Maintain
•Stop
Loss of signal set-
point
4239 % 20.0 0.0 200.0 Loss of signal preset speed.
Parameter ID Units Default Min Max Description