Perfect Harmony GENIII/e User’s Manual The Keypad and Display Interface
A1A19000405A: Version 1.3 3-47
3
Table 3-37: Auxiliary Input #1 Menu (4500)
Parameter ID Units Default Min Max Description
Source 4510 Off
Auxiliary input source
•Off
•Ext 1-3
Type 4520 4 – 20mA
This parameter sets the operational mode
for auxiliary input 1.
• 0 - 20mA
• 4 - 20mA
• 0 - 10V
Min input 4530 % 0.0 0.0 200.0 Minimum auxiliary input
Max input 4540 % 100.0 0.0 200.0 Maximum auxiliary input
Loss point
threshold
4550 % 15.0 0.0 100.0
Threshold where loss of signal action is
activated.
Loss of signal
action
4560 Preset
Select loss of signal action.
•Preset
• Maintain
•Stop
Loss of signal
setpoint
4570 % 20.0 0.0 200.0 Loss of signal preset speed.