The Keypad and Display Interface Perfect Harmony GENIII/e User’s Manual
3-48 A1A19000405A: Version 1.3
s
s
ss
3
Table 3-38: Auxiliary Input #2 Menu (4580)
Table 3-39: Analog Outputs Menu (4660)
Parameter ID Units Default Min Max Description
Source 4590 Off
Auxiliary input source
•Off
•Ext 1-3
Type 4600
4 – 20mA This parameter sets the operational
mode for analog input 1.
Min input 4610 % 0.0 0.0 200.0 Minimum auxiliary input.
Max input 4620 % 100.0 0.0 200.0 Maximum auxiliary input.
Loss point threshold 4630 % 15.0 0.0 100.0
Threshold where loss of signal
action is activated.
Loss of signal action 4640 Preset
Select loss of signal action.
•Preset
Maintain
•Stop
Loss of signal setpoint 4650 % 20.0 0.0 200.0 Loss of signal preset speed.
Parameter ID Units Default Min Max Description
Analog Output #n* 4660+4(n-1)+1 Submenu
ID of submenu for Analog
Output #n (n=1-16)
Analog variable 4660+4(n-1)+2
Total
Current
This variable sets the input
source for analog output
#n. See Table
3-40.
Output module type 4660+4(n-1)+3 Unip
Sets the output type for the
module.
Unip (Unipolar)
Bip (Bipolar)
Full range 4660+4(n-1)+4 % 0.0 0.0 300.0
Scales the output range of
the variable selected.