The Keypad and Display Interface Perfect Harmony GENIII/e User’s Manual
3-52 A1A19000405A: Version 1.3
s
s
ss
3
Table 3-44: Comparator Setup Menu (4800)
Table 3-45: Compare 1-32 Setup Menu Parameter Descriptions
Table 3-46: Variable Pick List for Comparator Setup Submenus
Submenu Description
Comparator n Setup
Submenus that contain 32 sets of comparators for custom use in the system program.
Each comparator set (Compare 1 through Compare 32) consists of three parameters
that are located in the comparator setup menus. Comparators are system program
flags (Comparator1_I through Comparator32_I) which can be used anywhere within
the system program environment to control software switches. Refer to
Table 3-45.
Menu Item Default Value Description
Comp n A in variable select
(list) (n=1-32)
Manual value
“Comp n A” and “Comp n B” inputs can be selected from the
list in Table
3-46.
Comp n B in variable select
(list) (n=1-32)
Manual value
The comparator flag compar_n_f (where n=1-16) in the sys-
tem program is set true if “Comp n A in” > “Comp n B in”.
Comp n manual value 0.0% Min: -1,000% Max: 1,000%
Compare n type (list) (n=1-
32)
‘Mag’ if n=1;
‘Off’ if n>1
“Compare n” can be set to the following:
signed (e.g., 10 > -50)
magnitude (e.g., -50 > 10)
disabled (no compare is done)
Analog Input 1 Analog Input 13 Motor speed
Analog Input 2 Analog Input 14 Motor current
Analog Input 3 Analog Input 15 Enter Manual Value
Analog Input 4 Analog Input 16 Manual ID
Analog Input 5 Analog Input 17 Max Avail Out Vol
Analog Input 6 Analog Input 18
Analog Input 7 Analog Input 19
Analog Input 8 Analog Input 20
Analog Input 9 Analog Input 21
Analog Input 10 Analog Input 22