Sensitivity
The sensitivity of 7SR46 Argus Relay is 0.8 ⋅ I
smin
(minimum phase current) in 1-phase or 0.4 ⋅ I
smin
(minimum
phase current) in 3-phase. This minimum phase current is necessary for the healthy functioning of the relay.
The following graphs shows the sensitivity of the relay, In the absence of auxiliary power supply, the sensi-
tivity of the relay is the minimum phase current required for the relay to energize, detect a fault, and trip as
per the configuration.
[dw_sensitivity operating-time_Bo, 1, en_US]
Figure 2-4 Sensitivity for 1-Phase, 3-Phase with Binary Output and Pulse Output
i
i
NOTE
The main battery improves the sensitivity.
2.2
Device Functionality
2.2 Sensitivity
Reyrolle, 7SR46 Device, Manual 21
C53000-G7040-C103-1, Edition 10.2022