Binary Outputs
Overview
The 7SR46 Argus relay provides 2 binary outputs which can be configured to send commands to the switch-
gear units and indications for remote signaling of the important events and status.
The binary output can be assigned to any available functions under OUTPUT CONFIG > OUTPUT MATRIX
menu.
Binary Output Configuration
In default operating mode, the binary outputs are self-reset and remain energized until the triggering condi-
tion exists. The binary outputs can also be programmed to operate as hand reset.
Binary Output Logic
[lo_binary-output, 1, en_US]
Figure 2-6 Binary Output Logic
(1) OUTPUT CONFIG > OUTPUT MATRIX
(2) OUTPUT CONFIG > BO CONFIG
Binary Output Details
Table 2-7
Binary Output
Parameters Description Default
Value
Min Max Step Change
50-1 50-1 element operate 1
50-2 50-2 element operate 1
51-1 51-1 element operate 1
50N-1 50N-1 element operate 1
50N-2 50N-2 element operate 1
51N-1 51N-1 element operate 1
2.5
Device Functionality
2.5 Binary Outputs
26 Reyrolle, 7SR46 Device, Manual
C53000-G7040-C103-1, Edition 10.2022