Real Time Clock (RTC)
The time and date can be set either via the relay fascia using appropriate commands in the SYSTEM CONFIG
menu or using the Reydisp Evolution software. When the relay is de-energized, the battery maintains the time
and date. If battery is low or not available in the relay, then relay does not sync the time and date.
i
i
NOTE
Device date and time must be set after firmware update or when the device is commissioned.
The relay can be synchronized to the nearest second or minute using Reydisp Evolution software. The device
can have a drift of ± 6 s/day.
Table 2-8 Real Time Clock
Attribute Value
Accuracy (-10°C to 60°C) ± 70 p.p.m
The default date is set as 01/01/2021 to indicate that the date is not set. In the relay, only the hours and
minutes can be edited. When you press ENTER after editing the seconds, seconds are set to 0 and the clock
starts.
By default, the clock follows a 24-hour format for time and DD/MM/YYYY format for date.
2.10
Device Functionality
2.10 Real Time Clock (RTC)
34 Reyrolle, 7SR46 Device, Manual
C53000-G7040-C103-1, Edition 10.2022