This setting is used to allow the element to be switched on and off if it is not required. An individual setting is
provided for each element. This setting can be used to select the number of elements required.
Parameter State Description
Disabled
The element is inactive.
Enabled
The element is active.
Gn 50N-n Setting
Default setting: 1.0 ⋅ I
s
This setting defines the operating current threshold of the element. The applied current must exceed this
setting by a factor of 1.00x for pickup of the element. The operation timing then depends on the selected
delay for the element setting. The element pickup resets when the current is reduced under the following
conditions:
0.2 ⋅ I
s
to 20.0 ⋅ I
s
is ≥ 90 % I
op
This setting should be set to suit the individual application
Gn 50N-n Delay
Default setting: 0.00 s
This setting is set to suit the individual application.
Gn 50N-n Inrush Action
Default setting: Off
High levels of inrush currents into reactive components, for example transformers; when they are switched in
can result in operation of elements. The inrush current can be detected by a high percentage of 2nd harmonic
current content by the 81HBL2 element. This parameter can be configured to inhibit the element automati-
cally.
Parameter Value
Description
Off The earth fault element is not inhibited by operation of the 81HBL2
element.
Inhibit The earth fault element is inhibited by operation of the 81HBL2 element
and automatically released when the 81HBL2 element resets.
Settings Example
There should be little or no current flowing to earth in a healthy system. So earth fault relays can be given far
lower pickup levels than relays which detect excess current above load current in each phase conductor. Earth
fault relays are important where the fault path to earth is a high-resistance one (such as in highly arid areas) or
where the system uses high values of earthing resistor/reactance as any earth fault current that flows in the
phase conductors is limited.
Settings Menu
CONFIGURATION > FUNCTION CONFIG
Parameter Setting Options Settings
Default Gn1 Gn2
Gn Derived E/F Disabled
Enabled
Disabled
CONFIGURATION > CURRENT PROT'N > DERIVED E/F > 50N-n
Parameter Setting Options Settings
Default Gn1 Gn2
Gn 50N-n Element Disabled
Enabled
Disabled
Functions
3.3 50N Instantaneous Earth Fault – Derived
42 Reyrolle, 7SR46 Device, Manual
C53000-G7040-C103-1, Edition 10.2022