Gn 50N-n Setting 0.2 ⋅ I
s
to 20.0 ⋅ I
s
Δ 0.01 ⋅ I
s
from 0.2 ⋅ I
s
to
4.0 ⋅ I
s
Δ 0.5 ⋅ I
s
from 4.0 ⋅ I
s
to
20.0 ⋅ I
s
1.0 ⋅ I
s
– –
Gn 50N-n Delay 0 s to < 20 s
Δ 0.01 s
0 s – –
≥ 20 s to < 100 s
Δ 0.1 s
≥ 100 s to 600 s
Δ 1 s
Gn 50N-n Inrush
Action
Off
Inhibit
Off – –
Information List
Input/Output Matrix User Logic Type IEC 103 Modbus RTU
Inhibit 50N-n Inhibit 50N-n Input – –
50N-n 50N-n Output Y Y
Functions
3.3 50N Instantaneous Earth Fault – Derived
Reyrolle, 7SR46 Device, Manual 43
C53000-G7040-C103-1, Edition 10.2022