51N Time-Delayed Earth Fault – Derived
Overview of the Function (51N)
The time-delayed earth fault protection is used to provide:
Detection of earth current in electrical equipment
Backup or emergency protection in addition to other protection functions or devices
Coordinated operation with other devices using time graded settings
Structure of the Function (51N)
The derived time‑delayed earth fault protection element has group-dependent settings. These settings can be
different in each settings group – group numbers (Gn) 1 and 2.
The function monitors the primary system earth current by calculating the sum of the 3-phase CT inputs for
example CT1/2/3.
The basic time‑delayed derived earth fault function (51N) is characterized by the following:
Current measurement is based on fundamental current.
A number of time versus current operate curves are selectable based on IEC and ANSI standards.
Alternatively, the 51N elements can operate with a definite time lag (DTL) characteristic.
LED operations are provided for earth fault. A general pickup and 51N‑n output are also provided.
Logic of the Function (51N-n)
[lo_7sr46_51N_TimeDelayedDerivedEFFn, 1, en_US]
Figure 3-5
Logic Diagram of Time-Delayed Derived Earth Fault Protection (51N)
3.5
Functions
3.5 51N Time-Delayed Earth Fault – Derived
50 Reyrolle, 7SR46 Device, Manual
C53000-G7040-C103-1, Edition 10.2022